Use the Event Scheduler Manager
Creat Event Schedules
Creat Sequences
Creat Event Condition
29 trang |
Chia sẻ: Mr Hưng | Lượt xem: 1049 | Lượt tải: 0
Bạn đang xem trước 20 trang nội dung tài liệu Mô phỏng công nghệ hóa học và dầu khí - Unit 9: Event scheduler, để xem tài liệu hoàn chỉnh bạn click vào nút DOWNLOAD ở trên
Nhóm Mô phỏng Công nghệ Hoá học và Dầu khí
Trường Đại học Bách khoa Hà Nội
Dynamic Modeling
using UniSim Design
Unit 9
Event Scheduler
Objective
Use the Event Scheduler Manager
Creat Event Schedules
Creat Sequences
Creat Event Conditions
2
Workshop
The Event Scheduler Manager contains all the Event
Schedules in the current Unisim Design Case.
Each Schedule is comprised of Sequences, which in turn
are made up of events.
An Event must have a Condition, which determined
when the Event has been triggered. At least one
condition must be fully defined for each event.
Once an event has been triggered, a series of pre-
defined Actions will be excuted.
A variety of action can be performed including closing
valve and switching controller mode, changing variable
value and switching to other sequences
3
Structure
4
Open Event Scheduler
Simulation menu
Using hot key Ctrl E
5
Button in the Schedule Options
Add: to add a new schedules to the case
Copy: to make a copy of the selected schedule
Delete: to delete the selected schedule
Import: to import a saved schedule from disk
Export: to export the selected schedule to disk
Sort: to arrange the schedules
6
Event Scheduler
1. Open case 08.TCDyn.usc
2. Open the Event Scheduler
3. Press Add Button
Rename the new schedule to High Liquid Lever
in HPSep
7
Event Scheduler
8
Event Scheduler
The event scheduler view has 3 checkboxes:
Smart Tree: Show the current Event of the last
selected sequence of schedule
Trace Messages: Enable the tracing of event
scheduler messages
Multi Events: to execute multiple continuous
events, with condition of true, in a single time
step
9
Event Scheduler
10
Event Scheduler
4. On the Schedule view, click the Add button to
creat a new sequence
5. Rename the Sequence to High Liquid Level
11
Event Scheduler
12
5 4
Event Scheduler
The Sequence field contains the name of sequence.
The Run Mode field displays the sequence mode;
one shot or continuous.
A One Shot sequence executes all ít Events in order then
its status changes to Complete
A continuous sequence return to the first event after the
last event has been executed, in a continuous loop.
The Event, Waiting for and Pending Actions fields
display the current event number with its
corresponding condition name and action list name.
13
Event Scheduler
6. Select the Sequence High Liquid Level from the
Event Scheduler tree view.
7. On the High Liquid Level sequence view, click the
Add button to creat a new Event. Change the
name from Event 1 to ESD Trip
8. Press the View button or select the Event from
the Event Scheduler Tree.
14
Event Scheduler
9. In the Wait For Box, select The Logic to Evaluate
True radio button
10. In the Condition Name field, rename the
condition to Level > %
11. Press the Add Variable button and add the PV for
the High Pressure Separator Level controller (LC-
HP Sep)
15
Event Scheduler
16
Event Scheduler
12. In the Logical Expression box type in the
expression: Var1 > 90%
This expression will evaluate as True if the level
controller PV is above 90%
17
Event Scheduler
18
11
7
9
Parameter Setting
ESD Trip State Unchecked
Trip Mode Trip Open
Invert ESD State Checked
Event Scheduler
13. On the Action List tab select the Add button.
Rename Action 1 as VLV- 100 ESD Trip
19
Event Scheduler
14. Configure the VLV- 100 ESD Trip action with type
Specify Variable and set the value so that when
the event runs the value trips open
20
Event Scheduler
21
14 13
Event Scheduler
15. An addition Event with two actions should be
added to the High Liquid Level Sequence
22
Variable Value
Purpose 10 mins after VLV- 100 opens,
the ESD Trip value is reset to 0
and the mode of LC is set to
auto with a SP equal to 50%
Condition Name Post ESD Trip
Condition Elapsed Time = 10 mins
Action List Name Reset Normal Condition
Event Scheduler
23
Variable Value
Action 1 Name VLV- 100 Normal
Type Specify Variable
Target VLV- 100 – ESD Trip
Value 0
Action 2 Name Reset LC to auto with SP= 50%
Type Set Controller Mode
Target LC- HP Sep
New Mode Auto
New SP 50%
Event Scheduler
24
Event Scheduler
16. Sort the events such that Post ESD Trip occurs
after the ESD Trip event.
17. Return to the Schedule View and change the Run
Mode from One Shot to Continuous
18. Press the Start Button
25
Event Scheduler
26
16
Event Scheduler
19. Save the case as 09.ES.usc and start the intergrator
20. Arrange for level in the HP separator to rise to 90%.
Note if controller LC- Hp Sep overshoots during
event Post ESD Trip and the PV rises above 90%, it
will trigger the ESD Trip events again
If this happens, re-tune controller LC- HP Sep
(increase Kc) to avoid this
Save case
27
Event Scheduler
28
Challenge
Set up a new event within the High liquid Level
Sequence, which performs the actions of step 20
(i.e. causes the liquid level to rise to 90%) after an
alapsed time equal to 15 mins.
This new Event will cause the sequence to cycle
continuously.
29